TV28N

2.8m sampling tube

TV - Air-sampling tube - The air-sampling tube is available in three different lengths: 0.6m, 1.5m, 2.8m. It should be chosen in accordance with the width of the duct concerned. The sampling tube must traverse at least 90% of the duct. If the duct is wider than 60cm, the sampling tube must traverse the entire duct.

Installation - the aluminium sampling tube can be easily shortened to adapt to the duct. The diameter of the hole for the air-sampling tube is 38mm.

Air-flow monitoring -The adaptor is fitted with a red plastic tongue which indicates the air flow to the detector and thus provides confirmation that there is no leakage and that the air flow from the duct is passing through the housing.

Related products

DDHF1/10 N

DDH204

DDHCOVERN

DDHBRKTN: