View

Via the main menu it is also possible to visualize the status of different parts of FA100:

Installer PIN code, Main menu, Info

This section provides access to:

  • Detectors, section where it is possible to view, after selection, the current values of each of the available detectors:

    • Obscuration level, percentage of smoke detected with respect to the alarm threshold

    • Reliability rate, a value that indicates the presence of particles with a diameter of less than 1 µm in the aspirated particulate.

      These particles characterize a fire and allow this situation to be discriminated against false alarms due to misleading phenomena (e.g. dust).

      The value ranges from 0 to 200; the maximum value indicates the minimum probability of a false alarm.

    • Contamination level, level of contamination of the detector module from dust, particles, etc.

    • Airflow rate, aspirated, in l/min

    • Temperature

  • WiFi, section for WiFi connection diagnostics:

    • Mode, selection of the operating mode of the “Transceiver station” or “Access point” (see “Connection”)

    • IP address, IP address associated with FA100

    • Gateway, IP address of the gateway.

    • Network mask

    • MAC address

    • Connection, when the selected operating mode is “Transceiver station”, the status of the connection to the Wi-Fi network will be displayed; when the selected operating mode is “Access point”, the list of network devices connected to FA100 will be displayed

  • Ethernet, section for Ethernet connection diagnostics:

    • IP address, IP address associated with FA100

    • Gateway, IP address of the gateway.

    • Network mask

    • MAC address

  • I/O, section where you can view the characteristics of the 4 I/O terminals with which the FA100 motherboard is equipped. For each terminal it is possible to read, after selecting it:

    • Description, customizable label used to identify the terminal

    • Direction, whether input or output

    • Polarity, normally open / normally closed

    • Reference, input referred to negative (ground) and to positive (+24V)

    • Status, visualization of the terminal status (active, reset/stand-by, interconnection fault)

  • Relay, section where it is possible to view the characteristics of the 6 Relay terminals with which the FA100 motherboard is equipped. For each terminal, after its selection, it is possible to read:

    • Description, customizable label used to identify the terminal

    • Status, visualize the terminal status (active, reset/stand-by)

  • Power supply, section where you can view the current voltage of both the primary power supply, supplied via the “PRIM” terminals, and the auxiliary power supply, supplied via the “AUX” terminals.

  • Firmware version, section where it is possible to consult the firmware revision installed on the FA100 motherboard, loop interface and detectors in use.

    In this section it is also possible to view the version of the programming data (it is increased with each programming change).

  • Serial numbers, section where it is possible to consult the serial number of the FA100 motherboard, loop interface and the detectors in use.