Output group parameters
-
Label – 20 character string that the control panel will use to identify the group of outputs.
The
button accesses viewing of the group index list (not editable). -
Activation delay – delay in seconds before actual activation of the group.
This delay applies only to alarm status, the timeout starts from the moment a group activation condition is activated. The group activates effectively when the set delay ends. -
Activation duration – if the “Pulse” option is enabled, this is the time, expressed in seconds, after which, once activated the group will automatically deactivate.
-
If in pre-alarm pass automatically to alarm after – this is the time, expressed in seconds, after which, once the group enters pre-alarm status it will automatically pass to alarm status.
Never – this option can be used to avoid the automatic transition from pre-alarm status to alarm status.
-
No manual activation – if enabled, this option prevents the group outputs from being activated manually.
-
Type B Correlation – if enabled, the alarm signal will activate only after two points belonging to the zone are activated.
The first point generates a pre-alarm signal without any time count.Once enabled, it is possible to select from the “Logic mode” field the activation coincidence mode between the two points, if the two points are part of the same control panel or the same network.
-
REI door mode – if enabled, the activation of the group occurs if the devices that activate the group are in “alarm”, “fault” or “disabled” status.
-
Repeat shared group setting – via these two options you can define the group as “shared”.
In this way the status of the selected group will be replicated for all the control panels in the same cluster or also for all the control panels of all the clusters. Therefore, if these options are enabled, the enablement will apply to all the control panels involved.
-
Audio zones activation with scenario – field for the selection of the audio scenario, from the four available, to be assigned to the audio zones belonging to the selected group.